The Las Vegas NNN Lease Checklist: 7 Rooftop HVAC & Flat-Roof Liabilities Tenants Miss

How commercial tenants and tenant-rep brokers uncover hidden mechanical and envelope bills before executing an "As-Is" Triple-Net or Modified-Gross lease in Clark County.

Why "Clean Paint and New LVP Flooring" Tells You Nothing About NNN Risk

Walk into a freshly white-boxed retail suite on West Sahara, a medical condo in Henderson, or a flex-industrial bay in Spring Valley and everything at eye level looks move-in ready. The real financial exposure in a Las Vegas Triple-Net (NNN) lease lives 22 feet overhead—above the acoustic drop ceiling and out on the sun-baked roof membrane.

Under standard Nevada commercial lease language, once you sign the possession acknowledgment, you typically inherit 100% maintenance and replacement responsibility for the dedicated HVAC units, electrical subpanels, and interior plumbing serving your suite—plus pro-rata Common Area Maintenance (CAM) pass-throughs for roof repairs unless explicitly excluded. Here are the seven liabilities to verify before lease execution.

1. Rooftop Package Units (RTUs) Past Year 12 or Running R-22

Every packaged rooftop AC unit carries a stamped serial plate encoding its exact manufacture month, year, tonnage, and refrigerant type. In Southern Nevada, a 14-year-old RTU running phased-out HCFC-22 (R-22) refrigerant is a ticking capital expense. A single grounding compressor failure in July cannot be economically repaired with R-22—requiring a full unit, crane lift, curb adapter, and electrical whip replacement running $14,000 to $28,000+.

2. Cracked Heat Exchangers & Disconnected Economizers

Because prospective tenants tour suites during mild spring or scorching summer afternoons, almost nobody tests the gas heating cycle on a Las Vegas RTU—until December arrives and an aluminized-steel heat exchanger with rusted-out cells trips rollout safeties or introduces carbon monoxide into the supply plenum. Likewise, seized outdoor-air economizer dampers waste thousands of dollars in annual NV Energy electric bills.

3. Missing Condensate P-Traps & Rusted Drain Pans

Negative-pressure commercial RTU blower compartments require a properly sized condensate P-trap. Without one, high-velocity blower suction holds condensate water inside the internal pan during operation—until the thermostat satisfies, the blower shuts off, and three gallons of water dump straight onto your new acoustic ceiling grid and retail inventory.

4. Compromised RTU Roof Curbs, Pitch Pans & Neighboring Grease Fans

Even when the landlord retains structural roof deck responsibility, NNN leases routinely bill leaks at "tenant equipment penetrations" directly to the tenant—or pass general roof patching through CAM charges. Even worse: if your suite sits adjacent to a restaurant whose rooftop upblast grease fan lacks a grease containment system, animal fats chemically dissolve TPO and modified-bitumen membranes across neighboring bays.

5. Maxed-Out 3-Phase Subpanels & Unpermitted Prior-Tenant Wiring

Before signing a lease for a medical clinic, fitness studio, cafe, or light-manufacturing bay, verify the exact service rating (e.g., 125A vs. 200A vs. 400A at 120/208V 3-phase) and inspect inside the deadfront cover. Prior tenants frequently leave behind double-tapped breakers, open junction boxes above the T-bar ceiling, flexible extension cords used as permanent wiring, or bonded neutrals inside subpanels.

6. Failed Pressure Reducing Valves (PRVs) & Aging Commercial Water Heaters

Clark County municipal water pressure regularly exceeds 80–105 PSI in Henderson, Summerlin, and southwest hillside corridors. When a suite's brass PRV fails wide open, excessive static pressure ruptures flexible lavatory supply lines, coffee/filtration equipment solenoids, and commercial water heater tanks overnight when the suite is unoccupied.

7. ADA Restroom & Entrance Hardware Exposure

Many commercial leases obligate the tenant to pay for code/ADA upgrades triggered by the tenant's business license or TI permit application. Checking restroom grab-bar geometry, lavatory knee clearance, door closer sweep speed, and threshold transitions before signing lets your broker allocate existing barrier corrections to the Landlord's Work Letter.

Turn Findings Into Lease Leverage Explore our dedicated Las Vegas Triple-Net (NNN) Lease Baseline Assessment page or connect with our commercial desk to align pre-lease due diligence with your brokerage workflow.

NNN Lease Checklist FAQs

What is a reasonable HVAC repair cap to negotiate in a Las Vegas NNN lease?

While every lease negotiation depends on market leverage and tenant improvement (TI) allowances, many Clark County tenant-rep brokers negotiate either a full Landlord 12-month warranty on existing RTUs or an annual tenant HVAC repair/maintenance cap of $1,000 to $1,500 per unit per year, with capital replacements amortized over a 10-to-12 year useful life rather than charged 100% upfront to the tenant.

How long do commercial rooftop HVAC units actually last in Las Vegas?

Although national ASHRAE tables cite a 15-year median service life for packaged rooftop units, extreme Mojave Desert ambient temperatures (110°F–117°F) and heavy summer runtime frequently trigger major compressor or condenser-fan failures between years 11 and 14 when quarterly coil cleaning has been neglected.